Ventilation Hoods - Test Lab
A little explanation is needed to clarify this table. The face velocity is a measurement at which the hood sash should be lowered or raised in accordance to JLAB's policy. The standard at JLAB is 100 fpm, thus the height of the hood sash in inches should represent the measurement at this value. So, if the face velocity for any given hood at 100fpm is 12.45, the hood sash should only be 12.45 inches from the bottom of the hood opening.
Building 58
Bldg/Room Description Face Velocity fpm/inches 58/108 Paint Hood 80fpm: 17.6 100fpm: 14.1 120fpm: 11.7 58/Offline Chem Chemical Fume 80fpm: 13.1 100fpm: 10.5 120fpm: 8.7 58/Offline Chem Chemical Fume 80fpm: 17.8 100fpm: 14.2 120fpm: 11.9 58/Offline Chem Chemical Fume 80fpm: 18.3 100fpm: 14.7 120fpm: 12.2 58/Production Chem Chemical Fume 80fpm: 17 100fpm: 13 120fpm: 11 58/Production Chem Chemical Fume 80fpm: 17.8 100fpm: 14.2 120fpm: 11.9 58/286+289 Soldering Station 100fpm at 5 inches 58/286+289 Soldering Station 100fpm at 5 inches 58/286+289 Soldering Station 100fpm at 5 inches 58/Welding Area Soldering Station 250fpm at 5 inches 58/274 Soldering Station 100fpm at 5 inches
Building 59
Bldg/Room Description Face Velocity fpm/inches 59 Solvent Fume Hood 80fpm: 16 100fpm: 12 120fpm: 10
*Red number indicates JLAB Standards