Appendix T3 Electrical
Classification Guidelines |
||
|
|
|||
These guidelines are based on common gas system
installations at Jefferson Lab which have been analyzed. The classification shall be determined for
each specific installation. All areas are assumed to be NEC Class 1, Group D.
1)
Enclosed gas storage and
mixing sheds are Division 2. This is based on adequate ventilation, this
standard, and that a flammable mixture is likely to be present in the
atmosphere less than ten hours per year.
2)
A sphere with a diameter of
1.5 meters around outdoor vents is Division 1. A sphere with a diameter of 3 meters
is Division 2. Generally there would be no electrical equipment in this area.
3) A sphere with a diameter of 1 meter is Division 1 around indoor vents. A sphere with a diameter of 2 meters is Division 2.
|
|