TITLE:

ES&H Manual

 

DOCUMENT ID:

6210 Appendix T1

Ground-Fault Protection

 

 

1.0          Introduction

 

An important part of ensuring the safety of electrical equipment is maintaining appropriate insulation and a reliable ground.

 

This appendix discusses the purposes of good insulation and proper grounding.  It also outlines the appropriate use and maintenance of ground-fault circuit-interrupters (GFCIs).

 

2.0          Grounding and Insulation

 

All electrically-powered tools and appliances that meet the safety criteria of a Nationally Recognized Testing Laboratory (NRTL) – and these are the only devices we should purchase – have built-in provisions for safeguarding against electrical shock in normal use, for the intended purpose and application.  NRTL listing for residential use is meaningless, for example, if the device is used for more severe commercial or industrial purposes.  Use a “household” appliance in a manner consistent with home uses.  Information about NRTL approval limitations is found on the approval label.

 

·       Electrical insulation is a non-conductive layer of material between you and the energized components.  Its composition and thickness are selected for that particular application.  It cannot be modified without invalidating the NRTL listing or approval.  Double-insulated tools and appliances have two, independent layers of insulations, one of which may be the exterior case.  Insulation is reliable unless it is damaged by impact damage, heat, chemicals, or tampering.  Most insulation will not prevent an electric shock if the device gets wet.

 

If you detect any deterioration of outer jackets, cases or cabinets, or you suspect that the insulation or barriers have been impaired, immediately take the device out of service.  Inform your supervisor and area safety warden or ESH&Q staff.

 

·       Grounding an appliance or tool provides a safe path for stray currents that may result from an internal fault.  It requires a third conductor in the appliance cord and in any extension cord and branch circuit into which it is plugged.  Ground prongs on plugs lead a hard life.  They are the longest blade, and they often get damaged by chronic physical abuse, including “whipping” the plug out of the receptacle.  Since ground conductors are not needed for the device to operate, there may be an undetected open ground in an appliance, its cord, or in a branch circuit.  For this reason, it is important to test grounded appliances, and circuits periodically for ground continuity.  Your supervisor or ESH&Q staff can perform or arrange for this test

 

Never ignore any indication – slight tingling during use, for example – that a ground is not intact.  Cease the work, and get help.  Never use a cord that has a missing ground prong, and never use a “cheater plug” (as shown below) adapter at Jefferson Lab.  As a safety feature, extension cords and most appliances have polarized plugs (one blade wider than the other).  These special plugs are designed to prevent electric shock by properly aligning circuit conductors.  Additionally if the ground prong connection from a portable GFCI in series with an extension cord is faulty, the GFCI protection is ineffective.  Extension cords should be inspected and tested periodically.  See ES&H Manual Chapter 6120 Hand and Power Tools for more information on cords.

 

Figure 1.  Cheater Plug

 

3.0          Ground-Fault Circuit Interrupters (GFCIs)

 

A GFCI is one of the most effective means available for preventing electrical shock.  These devices are specially constructed circuit breakers or receptacles, and they open the circuit when they detect a very small imbalance in the current between the two active conductors.  This imbalance means that current is leaking to an unwanted ground connection – perhaps through your body.  Unlike conventional circuit breakers and line fuses; individual branch-circuit GFCIs open the circuit at currents well below those capable of causing electrical injury: about 5mA.  Be aware, however, that you may be sufficiently startled by contact with a GFCI-protected circuit that you may react reflexively; you can fall from a ladder, for example.

 

National Electrical Code (NEC) requires permanent GFCI protection for many potentially hazardous locations.  Occupational Safety and Health Administration (OSHA) requires GFCI protection for electrical service in construction environments.  Jefferson Lab requires GFCIs in all new installations where they are required by code and standards.  These include the following:

 

·       Restrooms, kitchenettes, laboratories, and other locations where receptacles are within six feet of sinks or showers

·       Exterior and rooftop receptacles

·       Electrical heating equipment on pipes and vessels (heat tapes, for example)

 

Temporary ground-fault protection shall be provided whenever appropriate by using portable GFCIs and cord sets with built-in GFCI  devices.  Typical applications:

·       Outdoor use of power tools where permanent GFCI  receptacles are unavailable

·       Garages and sheds

·       Other Locations where personnel may contact electrical systems while in contact with water.

 

Portable GFCIs are a better option for protection in areas that are infrequently occupied.  Testing the portable device takes much less time than visiting many locations to test seldom-used permanent GFCI receptacles or breakers.

 

GFCI shall be used in other locations where they would be beneficial.  This includes:

·       For any use of 120 VAC portable cords (extension cords) when cords are used in shops, in labs, in service buildings, and in the experimental halls and tunnels.  This protection may be provided by the use of a GFCI-protected outlet or by a portable GFCI-protected cord or cord adapter plugged into a non-GFCI outlet.

 

This does not apply to portable cords or surge protector cords used in an office environment or to provide temporary power to equipment in the accelerator tunnel which would not be accessible to reset the GFCI during beam operations.

 

 

Very large ( 1000A) circuit breakers are usually equipped with ground fault features.  The trip setting for these are much too high for personnel protection, however.  They are known as ground fault equipment protection (GFEP) and are meant to protect equipment and cabling.

 

3.1            Selection, installation, and identification of GFCIs

In order for GFCIs to be effective, they must be selected correctly for the applications and installed properly by qualified Jefferson Lab or subcontractor staff.

 

Receptacle GFCIs are often preferable to circuit breaker types.  Circuit breaker trips “kill” the entire circuit; a GFCI receptacle can be configured to protect only the devices plugged into it or those receptacles in a longer branch circuit.

 

Additional receptacles protected by GFCIs should be verified and marked accordingly by the installer.  An acceptable method is to affix a small decal to the cover plate with the message “GFCI Protected” or “GFCI.”  This informs others that the receptacle provides ground-fault protection when it is needed, and it cautions people from plugging in equipment (such as a computer) that does not need the protection and can be affected adversely by test and unplanned trips.

 

Circuit GFCIs trip at 5mA.  Substation GFEP are intended for equipment protection, not people protection, and trip at much higher currents.

 

A GFCI Receptacle may be reset once if it has tripped, anymore than one time requires troubleshooting by a qualified individual.

 

3.2            GFCI testing

All GFCI manufacturers recommend that their devices be tested at least monthly to ensure they operate as designed.  Using the “Test” button to verify trip action and then resetting a GFCI fulfills the testing requirement.  The most effective test method is via a special plug-in device that indicates if the receptacle is wired correctly and that induces an actual fault when a test button is pressed.  An improperly wired GFCI may not provide any protection or may fail to trip under test.  An open ground, for example, prevents the tester from inducing the fault condition.  Always look first for proper wiring as indicated by the device’s display lights.  GFCIs usually, though not always, fail in a mode that prevents them from carrying a load.

 

If the GFCI fails to trip or if it cannot be reset, notify the area safety warden or initiate a facilities management work request.

 

There is no special expertise required for GFCI testing.  The occupants of the area or the most frequent users of the GFCI are often the best ones to test the device.  Alternatively, safety wardens and others who perform routine workplace inspections could include GFCI testing as part of their activities.  It is the responsibility of the owner division of a work area to ensure that the test gets done.

 

Figure 2.  GFCI Tester

 

 

 

ISSUING AUTHORITY

APPENDIX AUTHOR

APPROVAL DATE

EFFECTIVE DATE

EXPIRATION DATE

REV.

 

 

 

ESH&Q Division

Todd Kujawa

12/09/03

12/09/03

12/09/06

0

 

This document is controlled as an on line file.  It may be printed but the print copy is not a controlled document.  It is the user’s responsibility to ensure that the document is the same revision as the current on line file.  This copy was printed on 3/23/2009.