Fire Protection Manual

Chapter 4, testing procedures

 

 

 

 

 

 

Appendix 8:  Examining Ionization & Photoelectric Smoke Detectors

 

 

 

 

1.0           Purpose

This document provides a procedure for conducting periodic testing of a fire-detection device required by NFPA 72, National Fire Alarm and Signaling Code®, Table 14.4.3.2 Device 17(7)(h).

2.0           Scope

All Ionization and Photoelectric Smoke Detectors shall be tested, per this procedure, on an annual basis.

3.0           Planning

Notify the facility work coordinator using the approved electronic work control notification procedure. Allow one week for approval of the requested work; be prepared to reschedule the requested work to satisfy the area’s production schedule. 

Testing requirements include:

·       2 staff members

·       amount of time is quantity-dependent

·       equipment

o   Detector Manufacturer’s O & M Manual (see 8.0 below)

o   Safe Guard Aerosol Smoke Tester

o   Device Analog Voltage Table

o   Ionization or Photoelectric Smoke Detector Data Sheet

4.0           Test Preparation

4.1           Establish the fire-detection system impairment using Chapter 5:  Fire Protection System Impairment Procedure for detailed instructions on work planning, advanced notification, and administrative controls.

4.2           Post the Fire Alarm Systems Testing in Progress sign(s).

4.3           Invite the technical representative (TR) to witness the test.

4.4           Evacuate the hazard area of all personnel.

4.5           Station a knowledgeable technician at the Fire Alarm Control Panel (FACP).

4.6           Disconnect the building audible alarms at the FACP.

4.7           The technician is to remain attentive at all times that the audible alarms are disconnected.

4.8           In the unlikely event an unanticipated fire alarm signal is received on the FACP, the technician shall reconnect the building audible devices and join the building evacuation.

5.0           Conduct the Test

5.1           Record the detector’s serial number and location on the Data Sheet.

5.2           Check the condition of each detector for signs of damage; verify the sensitivity of each detector using the List Sensitivity menu.

5.3           Refer to the Device Analog Voltage Table for a list of acceptable detector sensitivity ranges.

5.4           If the Partial System Disable LED is lit, use the Control Ann/Dis menu to check that all appropriate detectors are armed.

5.5           Activate a detector using the Safe Guard Aerosol Smoke Tester.

5.6           Verify alarm conditions are indicated in the following locations:

·       detector LED illuminates;

·       building address and proper indication at the FACP;

·       alarm viewer and associated graphic display; and,

·       an alarm condition is indicated on the Fire Marshal’s pager.

5.7           Verify that the alarms can be acknowledged and that the system can be silenced and reset.

5.8           Place a “Tested” sticker (with the date and technician’s name) on the detector housing.

5.9           Document results on the Ionization or Photoelectric Smoke Detector Data Sheet.

6.0           System Restoration

6.1           Reconnect the building audible alarms at the FACP.

6.2           Dismiss the assisting technician at the FACP.

6.3           Remove the Fire Alarm Systems Testing in Progress notification signs previously posted.

6.4           Notify the TR that the tests are complete and the system is on-line and operational. 

6.5           Allow the TR to verify that the system is in normal operating condition.

6.6           Allow personnel to return to the area previously designated as hazardous.

7.0           Conclusion

Upon completion of the procedure, the Ionization or Photoelectric Smoke Detector is on-line and operational.

8.0           References

·       Detector Manufacturer’s O & M Manual; MAINTENANCE Section

·       NFPA 72, National Fire Alarm and Signaling Code

9.0           Revision History

rev

summary

date

1.0

triennial review

-  updated

-  header and footer per discussion with T. Minga, 05.05.2022;

-  9.0 per footer dates, as well as format of 9.0;

-  made general edits and format updates (e.g., bullets, spacing, etc.)

-  corrected acronyms and abbreviations (e.g., SOTR to TR)

-  replaced previous red-boxed links with more up-to-date red-outlined box links (see below)

05.19.2022

0.2

periodic review; updated author and Fire Protection Manager from E. Douberly to T. Minga

06.02.2019

0.1

periodic review; minor edits

06.02.2016

0.0

initial release

06.15.2011

 

 

 

 

 

ISSUING AUTHORITY

AUTHOR

APPROVAL DATE

NEXT REVIEW DATE

rev

 

 

Fire Protection Department

Tim Minga

05.19.2022

05.19.2025

1.0

 

This document is controlled as an online file.  It may be printed but the print copy is not a controlled document.

It is the user’s responsibility to ensure that the document is the same revision as the current online file.  This copy was printed on 5/19/2022.