next up previous
Next: Operating the Buffer Dewar Up: Lists of Devices Previous: Serial Devices


Relay Controlled Devices

Several devices, such as solenoid valves, are switched on and off (or open and closed) by toggling relays. In most instances, a 120 VAC latching relay is used, which in turn is controlled by the normally open contacts of two, momentary 5 V relays from a VME relay board (VMIc2232). For instance, one 5 V relay is used to energize the 120 V relay, and thus open a solenoid valve. A second 5 V relay deenergizes the 120 V relay, and closes the valve. Since the 5 V relays are momentary, the status of the solenoid does not change during an IOC crash or reboot. The position of the latching relay, and thus the valve, is read back into the computer using digital inputs located on the ADIO industry packs.

A list of the relay-controlled devices for the target, along with the digital readbacks, is tabulated below. Refer to the ADIO-IP and VMIc223 manuals for pin-out designations.




Device Action VMIc Relay Digital Readback
Solenoid Valves
SV91108 Open 16 ADIO 1, ZB0
  Close 17 ADIO 1, ZB1
SV91110 Open 18 ADIO 1, ZC4
  Close 19 ADIO 1, ZB3
SV91111 Open 20 ADIO 1, ZB4
  Close 21 ADIO 1, ZB5
SV91115 Open 22 ADIO 1, ZB6
  Close 23 ADIO 1, ZB7
SV91115A$^1$ Open 23 ADIO 1, ZB6
  Close 22 ADIO 1, ZB7
SV91148 Open 24 ADIO 1, ZC0
  Close 25 ADIO 1, ZC1
SV91149$^2$ Open 25 ADIO 1, ZC2
  Close 24 ADIO 1, ZC3
OVC Controls
PV91104 Open 2 ADIO 2, ZB0
  Close 3 ADIO 2, ZB1
OVP91130 Start 4 ADIO 2, ZB2
  Stop 5 ADIO 2, ZB3
MP91132$^3$ Start 6 ADIO 2, ZB4
  Stop 7 ADIO 2, ZB5
Warm Return Valve
EV9177$^4$ Direction 0 na
  Enable 1 na



$^1$The magnet exhaust/recycle valves, SV91115 and SV91115A are controlled by a single 120 VAC relay. One valve is controlled by the Normally Open set of contacts, the other by the Normally Closed set. Therefore, only one pair of 5 V VME relays and one pair of digital inputs are necessary.

$^2$The refrigerator exhaust/recycle valves, SV91148 and SV911149 are controlled by a single 120 VAC relay. One valve is controlled by the Normally Open set of contacts, the other by the Normally Closed set. Therefore, only one pair of 5 V VME relays are necessary. Two pairs of digital inputs are used.

$^3$MP91132, the backing pump for the oil diffusion pump, is not connected to a relay, but is left running continuously. The software controls do exist for remote control however.

$^4$EV9177, the warm return valve, is controlled by two static (non-momentary) 5 V relays. The first sets a direction (energize = CLOSE). The second enables valve motion (energize = MOVE).


next up previous
Next: Operating the Buffer Dewar Up: Lists of Devices Previous: Serial Devices
Christopher D. Keith 2001-08-23