Next: About this document ...
Up: GENmanual
Previous: Relay Controlled Devices
Operating the Buffer Dewar Controls
There are three valves directly connected to the 500 l
buffer dewar:
EV9180 (supply JT), EV9178 (cold return JT), and
EV9177 (warm return ball valve)
Incorrect operation of any of these valves is likely to disrupt
the 4 K liquid helium distribution system in Hall C and could
produce an ESR outage that would halt the experiments in all
three halls for many hours. Changes in the status of any of
these valves or the PID loops that control them should only be
made after consultation with:
Mike Seely |
|
Chris Keith |
|
Dave Meekins |
|
office: 269-5036 |
|
office: 269-5878 |
|
office: 269-5434 |
|
home: 223-1216 |
|
home: 596-3002 |
|
home: 874-4750 |
|
pager: 881-1194 |
|
pager: 888-4090 |
|
pager: 872-2442 |
|
The following conditions may indicate a problem with the buffer dewar
system:
- Incorrect liquid level in the buffer dewar
- The PID
loop is set to maintain this level at 65%. It will vary
under normal operation from around 60% to around 70%
during the fill cycle.
- Vapor plume at the top of the buffer dewar
- A pressure
excursion in the cold return line may cause the relief valve on the
buffer dewar to open. It may freeze open. A brief access
to the hall is necessary to warm the relief valve.
- Incorrect buffer dewar pressure
- The cold return JT valve
(EV9178) operates to maintain this pressure around
1300 mbar.
- High return temperature
- If the flow rate in the return line
falls too low, the return will warm up. The return temperature
TD9178 should never rise above about 6.5 K.
It has been our experience that the return line will stay below
this temperature as long as the supply valve EV9180
remains 35% or more open. PID loop EV9180A controls
the minimum allowed setting for EV9180 to keep the return
line at 5.8 K or below. However, attempting to maintain a
return temperature that is TOO low will result in minimum setting for
EV9180 that is too high. In this case the buffer dewar
may overfill.
- Oscillations in 4 K flow to the hall
- Sharp spikes or oscillations
on the 4 K helium flow to the hall frequently indicate that one
or more branches of the 4 K distribution piping is warm.
- Unusual valve settings
- The supply JT valve EV9180
is normally open 35-70%. The return JT valve is normally
around 50-70% open. The warm return valve is always closed.
Excursions much beyond these valve positions will produce alarms.
Next: About this document ...
Up: GENmanual
Previous: Relay Controlled Devices
Christopher D. Keith
2001-08-23