Fire Protection Manual

Chapter 4, testing procedures

 

 

Appendix 3:  Testing Radiant Energy Fire Detectors

 

 

1.0           Purpose

This document provides a procedure for conducting periodic testing of a fire-detection device required by NFPA 72, National Fire Alarm and Signaling Code®, Table 14.4.3.2 Device 17 (6).

2.0           Scope

This test shall be performed semi-annually on every Radiant Energy Fire Detector.

3.0           Planning

Notify the facility work coordinator using the approved electronic work control notification procedure. Allow one week for approval of the requested work, and be prepared to reschedule the requested work to satisfy the area’s production schedule. 

Testing requirements include:

-      2 staff members

-      time is dependent upon quantity of detectors

-      equipment

o   Fire Sentry Corporation O & M manual SP340, Rev. E

o   Approved flame simulator

o   Microfiber lens cloth

o   Radiant Energy Fire Detector Data Sheet

4.0           Test Preparation

4.1           Establish the fire-detection system impairment using Chapter 5:  Fire Protection System Impairment Procedure for detailed instructions on work planning, advanced notification, and administrative controls.

4.2           Post the Fire Alarm Systems Testing in Progress sign(s).

4.3           Invite the technical representative (TR) to witness the test.

4.4           Evacuate the hazard area of all unnecessary personnel.

4.5           Station a knowledgeable technician at the Fire Alarm Control Panel (FACP).

4.6           Disconnect the building audible alarms at the FACP.

4.6.1      The technician is to remain attentive for the full duration that the audible alarms are disconnected.

4.6.2      In the unlikely event an unanticipated fire alarm signal is received on the FACP, the technician shall reconnect the building audible devices and join the building evacuation.

5.0           Conduct the Test

5.1           Record the detector’s serial number and location on the Data Sheet.

5.2           Inspect physical condition of the detector and clean all viewing windows using the Microfiber cloth.

5.3           Verify that the detector is firmly mounted and that the detector's line-of-sight to the hazard area is not compromised in any way.

5.4           Activate each detector using the Fixed Sensitivity Flame Simulator.  Verify

5.4.1      that the detector LED lights.

5.4.2      proper indication at the local Fire Alarm Control Panel.

5.4.3      an Alarm Condition is indicated on the

                                                        i.         fire alarm workstation at security post 2,

                                                      ii.         alarm viewer and associated graphic display, and

                                                     iii.         Fire Protection Engineer’s pager.

5.5           Verify that the alarms can be acknowledged and the system can be silenced and reset.

5.6           Document results on the Radiant Energy Fire Detector Data Sheet.

5.7           Repeat steps 5.1 through 5.6 for remaining Radiant Energy Fire Detectors scheduled for testing at this time.

6.0           System Restoration

6.1           Restore the radiant energy fire detector and related signal monitoring equipment to normal.

6.2           Reset the local FACP.

6.3           Reconnect the building audible alarms at the FACP.

6.4           Dismiss the technician stationed at the FACP.

6.5           Remove the Fire Alarm Systems Testing in Progress signs previously posted.

6.6           Notify the TR that the tests are complete and the system is on-line and operational. 

6.7           Allow the TR to verify that the system is in normal operating condition.

6.8           Allow personnel to return to the area previously designated as hazardous.

7.0           Conclusion

Upon completion of the procedure, the Radiant Energy Fire Detector is on-line and operational.

8.0           References

-      Fire Sentry Corporation O & M manual SP340, Rev. E

-      NFPA 72, National Fire Alarm and Signaling Code

9.0           Revision History

rev

summary

date

1.0

triennial review

-  updated

-  header and footer per discussion with T. Minga, 05.05.2022;

-  9.0 per footer dates, as well as format of 9.0;

-  made general edits and format updates (e.g., bullets, spacing, etc.)

-  corrected acronyms and abbreviations (e.g., SOTR to TR)

-  replaced previous red-boxed links with more up-to-date red-outlined box links (see below)

05.14.2022

0.2

periodic review; updated author and Fire Protection Manager from E. Douberly to T. Minga

06.02.2019

0.1

periodic review; minor edits

06.02.2016

0.0

initial release

06.15.2011

 

 

 

 

 

ISSUING AUTHORITY

AUTHOR

APPROVAL DATE

NEXT REVIEW DATE

rev

 

 

Fire Protection Department

Tim Minga

05.14.2022

05.14.2025

1.0

 

This document is controlled as an online file.  It may be printed but the print copy is not a controlled document.

It is the user’s responsibility to ensure that the document is the same revision as the current online file.  This copy was printed on 5/14/2022.