TITLE:

ES&H Manual

 

DOCUMENT ID:

6200 Appendix T3

General Electrical Safety Guidelines

 

 

1.0            Purpose

 

This appendix provides an overview of general electrical safe work practices to be used by everyone at Jefferson Lab. It is recognized that increased awareness of these practices helps maintain an electrically safe work environment. 

 

2.0            Scope

 

This appendix describes the electrical safe work practices used during daily operations at Jefferson Lab. This guidance does not take the place of the need for work planning, control, and authorization.

This appendix is written in coordination to ES&H Manual Chapter 6200 Jefferson Lab Electrical Safety Program.

 

3.0            Responsibilities

NOTE:     Management authority may be delegated at the discretion of the responsible manager.

 

3.1              Everyone at Jefferson Lab

·         Perform work using electrical safe work practices.

·         Report electrical safety hazards to your Supervisor/Subcontracting Officer’s Technical Representative /Sponsor.

·         Submit a Facilities Management Work Request if new, repair, or maintenance electrical work is needed.

·         Report cases of electric shock to Jefferson Lab Occupational Medicine Department (x7539)

 

3.2              Qualified Electrical Worker

·         Provide electrical repair or installations upon request and supervisor approval.

·         Build, repair, and test power cords in accordance with Section 4.1 Power Cords.

 

3.3              Supervisor/Subcontracting Officer’s Technical Representative (SOTR)/Sponsor

·         Ensure compliance with safe electrical work practices.

·         Report electrical safety hazards to the appropriate authority.

4.0            Electrical Safe Work Practices

 

4.1              Power Cords

Power cords connect devices to power sources. They include extension cords, power strips, uninterruptible power supplies (UPS), and small appliances. Everyone at Jefferson Lab performs the following activities:

·         Check cords for external defects prior to use.

·         Discard those that are damaged. (Permanently disable the power source, by removing the cord end(s), prior to disposal.)

·         Turn device(s) “off” before connecting or disconnecting power source.

·         Keep cords out of the line of traffic. If unavoidable, use cord covers to prevent trip hazards and physical damage.

·         Avoid “daisy-chaining” power strips, one into another.

·         Extension cords can be “daisy-chained” as long as the cord wire gauge is sized adequately for the load to be served.

·         Ensure that cords have adequate air circulation when in use.

·         Fully insert all prongs into an outlet.

·         Grasp or pull the plug, not the cord, to remove it from an outlet.

 

4.1.1        Build

Only Jefferson Lab qualified electrical workers are authorized to field-assemble power cords for specific use(s).

 

4.1.2        Repair

Only Jefferson Lab qualified electrical workers are authorized to repair power cords.  The following criteria are used:

·         Determine whether repair is feasible/cost-effective. If not, properly dispose of the item.

·         Cords and ends are replaced with parts of equal or greater quality.

·         Electrical tape is never used to cover or repair damage to the outer jacket insulation; when the inner conductors are visible.

·         Repairs are checked to ensure conductors are connected to their proper terminal and for electrical continuity.

 

Nicks and abrasions, which do not penetrate completely through the outer jacket, are not considered a safety concern. Repair or replacement of the extension cord would not be required.

4.1.3        Types

4.1.3.1              Extension Cords

Extension cords are used to deliver power to a desired location on a temporary basis. 

·         Use as a temporary power supply.

·         Unplug and store out of the line of traffic when not in use.

 

4.1.3.2              Power Strips

Power strips, including strip plugs and surge suppressors, are used to provide power to multiple electronic devices at one time. Use the following safety guidelines:

·         Check the wattage rating to ensure compatibility with all devices connected to avoid overload.

·         Do not plug one power strip into another.

 

4.2              Uninterruptible Power Supply (UPS)

UPS (desk top sized) is a battery backup unit that supplies power when there is a sag in the normal 120 VAC power. These units have a potential for shock; even when the power cord is disconnected from the wall outlet, due to stored energy. Use the following safety guidelines:

·         Determination of Replacement – Contact the Computer Center (x7155) if assistance is needed to determine whether to replace the batteries or the unit. (If battery replacement is feasible, the work is to be done by a qualified electrical worker.)

·         Purchase – through Jefferson Lab’s WebStock system.

·         Disposal – Use Jefferson Lab’s Property Movement, Disposal or Transfer System:

o  Step 1 – Click on “Submit disposal/excess of "administrative" property not on your inventory

o  Step 2 – Complete the “Property to be excessed” form to generate a work order for the UPS to be picked up for disposal.

 

4.3              Ground-Fault Circuit Interrupter (GFCI)

GFCI is a device intended for the protection of personnel. It de-energize a circuit, or portion thereof, within an established period of time when current to ground exceeds approximately 6mA. A GFCI is required:

·         Per the National Electrical Code. They are installed in all new construction and renovation projects as required.

·         Where 125-volt single-phase; and 15- and 20-ampere receptacles are installed (i.e., bathrooms, kitchens, rooftops, outdoors, and within six feet of the outside edge of a sink).

·         For all receptacle outlets (including extension cords, and temporary wiring used to supply power to equipment during construction, remodeling, maintenance, repair, or demolition of buildings, structures, or equipment, or similar activities.)

·         For use with:

o   Cord-and-plugged vending machines (installed after 1/1/2005).

o   Electric drinking fountains (installed after 1/1/2008).

o   Portable generators – for all 125-volt single-phase 15-, 20-, and 30-ampere receptacles that are in use by personnel.

·         When supplying temporary power with the use of extension cords.

 

4.3.1        Testing GFCI

Jefferson Lab recommends that GFCI receptacles be tested in accordance with manufacturer’s recommendations; during safety warden inspections, and before using a temporary device that requires GFCI protection.

 

4.3.2        Types of GFCIs

4.3.2.1              Receptacle: A GFCI receptacle is used in place of a standard outlet (see Figure 1. GFCI Receptacle). These are generally found near water sources (e.g., kitchens, bathrooms, etc.).

 

Figure 1.  GFCI Receptacle

gfci receptacle1gfci receptacle2

 

4.3.2.2              Portable: A portable GFCI is used to provide temporary power from an unprotected outlet. They are tested prior to each use (see Figure 2.  Portable GFCIs).

 

Figure 2.  Portable GFCIs

Portable GFCI

 

4.3.2.3              Circuit Breaker: A GFCI circuit breaker controls an entire circuit on the main panel board. In the event of a ground fault, short circuit, or overload the breaker trips and shuts off electricity to the circuit. Only those persons who have been trained by a qualified electrical worker are authorized to reset GFCI circuit breakers.  Contact Facilities Management (x7400) for assistance if electricity is interrupted to your work area.

 

4.4              Switching (or resetting) circuit breakers   

Only those persons, who have been trained by a qualified electrical worker for the specific area, or equipment, are authorized to turn on/off or reset a circuit breaker. A minimal level of PPE, which varies between equipment types, is required during the switching operation.

Exception: During an emergency anyone at Jefferson Lab may turn on/off or reset a circuit breaker or disconnect switch as long as doing so does not put them at risk.

4.5              Housekeeping around electrical equipment

Do not store materials on top of electrical equipment (transformers, panelboards, utilization equipment…). Keep areas clear around electrical equipment to allow access for operation and maintenance. 

4.6              Capacitor Safety (storage & recycle)

Short capacitors in storage with a conductor securely fastened to the terminals and leave in place until the capacitors are returned to service. If a capacitor is scheduled for disposal, the short circuits shall remain in place.

4.7              Electrical Equipment Labeling

Panelboards, switchboards, and motor control centers are required to have an attached circuit directory (panel schedule) which clearly and legibly identifies the loads served. Spare circuits shall be identified as spares.

 

Equipment permanently connected to an AC source (circuit breaker) must have the equipment disconnect location clearly identified. Equipment which is fed from multiple power sources must clearly identify all sources of power.

 

All electrical equipment that poses a shock and/or arc flash hazard shall be labeled to warn persons of the potential hazard.

4.8              Abandoned Cable Management Practices

Abandoned cable is identified as a cable that is not terminated at both ends at equipment and is not identified for future use with a tag. All accessible portion of abandoned cable shall be removed. If a cable, or portion thereof, is unable to be removed or is selected to remain for future use then the cable should be identified with a cable tag and the cable should be insulated from contact with other live electrical wiring or devices.

4.9              Wall/Blind Penetration

Jefferson Lab buildings have electrical conduit, piping, and data/communications cable within their walls and imbedded in floor slabs.  It also has an extensive buried utility system on-site. Any work requiring penetration into walls, a floor, or soil, requires a Facilities Management’s Excavations and Blind Penetrations into Walls & Floors. Submit a Facilities Management Work Request to ensure compliance with this requirement.

 

4.10          Portable and Vehicle-Mounted Generators

GFCI protection is required for all 125 volt, single phase, 15-, 20-, and 30- ampere receptacles on portable and vehicle-mounted generators.  All other receptacle types require either GFCI protection or follow the National Electrical Code Equipment Grounding Conductor Program.

 

NOTE: The rules for grounding depend on the specific use and design of the auxiliary power generator. Therefore, if available, always refer to the manufacturers’ operation manual for further instructions.

 

5.0            References

 

·         Standards for Electrical Safety in the Workplace, NFPA-70E (2004)

·         National Electrical Code (NEC), NFPA-70 (2005)

 

6.0            Revision Summary

 

Revision 2.0 – 11/03/14 – Expanded Electrical Safe Work Practices to include bullets 4.4 – 4.10; updated reference to NFPA-70; deleted reference to IEEE and UL; per T.Kujawa.

Revision 1.1 – 11/19/10 – Added general electrical safe work practices for portable and vehicle-mounted generators per T.Kujawa.

Revision 1.0 – 05/10/10 – Updated to reflect current laboratory operations.

 

 

 

ISSUING AUTHORITY

TECHNICAL POINT-OF-CONTACT

APPROVAL DATE

REVIEW DATE

REV.

 

 

ESH&Q Division

Todd Kujawa

11/03/14

11/03/17

2.0

This document is controlled as an on line file.  It may be printed but the print copy is not a controlled document.  It is the user’s responsibility to ensure that the document is the same revision as the current on line file.  This copy was printed on 11/5/2014.