JLab_logo_text_white2

Fire Protection Manual

Chapter 2

Fire Protection Design

1.0           Purpose

This document outlines the considerations that need to be made to incorporate contemporary fire-protection standards, while accommodating the unique features of the accelerator, experimental apparatus, and a variety of associated workplace environments at Jefferson Lab.

2.0           Scope

This document describes personnel responsibilities, building fire-safety features, construction practices, fire protection systems selection, system acceptance, fire protection water supply, existing facilities, hazard prioritizations and mitigation, fire damage, actual loss determination, and loss reporting.

New facilities or major renovation of existing facilities requires a review of any existing fire-protection systems and features within the affected area by Facilities Management.  The design-review process includes reviews by a Fire Protection Engineer ([FPE] subcontractor) early in the design phase. These include reviews at the 30-, 60-, and 90‑percent design phase.  These reviews may be conducted on a less frequent basis, depending upon the size of the design project. Facilities Management maintains all relevant files for each project, including design criteria and rationale. Design reviews are also done for projects performed by in-house staff, with peer reviews performed for each design. 

Additional details regarding the design of new facilities are found in ES&H Manual Chapter 3110, Facility Design and Modification Review.

Equivalent means of Fire Protection and Exemption from prescriptive code requirements and DOE Orders are sometime warranted. This document is used to identify existing equivalencies and exemptions granted by DOE.

3.0           Responsibilities

Note:    Management authority may be delegated to a task-qualified TJNAF employee at the discretion of the responsible manager.

3.1           Fire Protection Engineer (FPE; synonymous with subcontractor)

·       performs building design evaluations

·       reviews and approves proposed projects and designs at multiple stages in the design process for compliance with fire protection code requirements and site-specific fire protection requirements

3.2           Supervisors, Building Managers and Area Work Coordinators

·       monitor the activities of personnel within affected areas

·       prevent any alteration to building construction features not coordinated with facilities management

3.3           ES&H Professionals 

·       ensure that space use is consistent with the fire safety design

·       provide guidance to line management on limitations of potential space use

·       participate, as required, in the planning processes for renovation and new construction

3.4           Facilities Management Staff

·       ensure fire protection water supply is adequate for design

·       incorporate all applicable codes, standard requirements, equivalencies, and exemptions into designs for new construction and renovation projects

4.0           Fire Safety Design Considerations

4.1           Building Design Evaluation

Building designs are evaluated for compliance with the traditional construction codes and standards.  Additional considerations include:

·       International Code Council Inc. International Building Codes

·       Site-specific requirements for detection, suppression, life safety, and underground-water distribution described in Chapter 1, Site-specific Requirements of this Manual.

·       Building features that provide for Highly Protected Risk status or the best-protected class of industrial risks. This status is achieved through incorporation of design features contained in FM Global Property Loss Prevention Data Sheets.

·       DOE STANDARD 1066-16 Fire Protection.

4.2           Fire Protection Water Supply

The City of Newport News provides water for the TJNAF site. The three water supply meter vaults at Jefferson Lab are:

·       a 4-inch water meter on Hogan Drive (north of the facility),

·       an 8-inch water meter on Jefferson Avenue (west of the facility), and

·       a 12-inch water meter on Canon Boulevard (south-east of the facility).

With the exception of the Support Service Center (SSC) Building area, the site hydrant and fire suppression systems are continuously connected to the Canon Boulevard and Jefferson Avenue underground 24-inch concrete city mains. This supply redundancy provides a high level of confidence in a continuous water supply for most of the site. The SSC area is served by the separate municipal water supply.

4.3           Equivalencies and Exemptions

4.3.1       Equivalency:  Common Path of Travel for Injector Area, Approved April 8, 1998 to exceed the maximum 100 ft distance for common path of travel (in an area protected by automatic sprinkler systems) by 15 ft for the injector area of the tunnel enclosure

4.3.2       Equivalency: Manual Pull Stations, Beam Enclosure, Approval letter from Barbara Morgan to Bill Rust dated April 21, 1995, permission to deviate from stations @ 200-foot intervals to stations @ 600-foot intervals

4.3.3       Equivalency: Fire Sprinkler Protection for Experimental Halls A,B,C, Approval Letter: September 27, 2010

Compensatory Action Required

·       Implement a comprehensive and rigorous Combustible Control Program: On February 8, 2011, Chapter 11, Combustible Loading, was created (and added to this manual) to develop a method to actively control the accumulation of transient combustible material in the Experimental Halls and the Accelerator Tunnel. Weekly inspections are conducted and documented (both electronically and in hard copy) by the FPE.

·       Install flammable gas detectors at locations where flammable gases are used: Currently in the process of evaluating the most up-to-date VESDA gas detection equipment to install in line of the existing VESDA piping.

·       Maintain existing active and passive fire protection features, more specifically, fire barriers, fire doors, sprinkler systems, VESDA, fire alarm and smoke removal systems:  Inspections are conducted per NFPA throughout the site by outside contractors.

·       Continue to have a qualified FPE serve on the experimental planning committee:  Both the Fire Protection Program Manager and the Fire Protection Engineer review all operational safety procedures as well as serve on the experimental planning committee.

4.3.4       Equivalency: Request (NFPA 101) Equivalency, Accelerator Tunnel Ramps, Approval Letter: February 4, 2008

Compensatory Action Required

·       Proposed design and facility operations shall include additional engineered and administrative safety controls listed below.

Engineered

o   Fire Detection system for early warning:  VESDA has been installed in the tunnel extension

o   Fire Suppression System:  Dry sprinkler system has been installed throughout the tunnel extension

o   Non-slip surface on the ramp:  Concrete floor was left in rough surface condition

o   Lifting eyes in the ceiling above the ramp to aid in material handling along ramp:  Lifting eyes have been installed throughout tunnel extension

o   Emergency Lighting:  Emergency lighting has been installed per NFPA requirements

Administrative

o   Restricted access to able-bodied personnel:  CANS will be installed for access control

o   Posted exit signs:  Exit signs are installed throughout the tunnel per NFPA

o   Personnel training:  SAF-113KD (Hall D Conduct of Operations) training incorporates Hall D and the tunnel extension into its program

o   Task hazard analyses of activities in the tunnel extension:  Task hazard analyses are conducted and approved before work moves forward in the tunnel

·       A change in the facility operations from the proposed scope of work voids the equivalency approval.     No plans at the present time to alter the scope of work

·       A change in the hazard classification within the specific area voids the equivalency.     No changes in the hazard classification in the specific area anticipated

·       Future revisions of the facility FHAs are to maintain a copy of the TJSO equivalency approval documentation and supporting JSA information within an attachment.     All FHAs from this point forward will have equivalency documentation incorporated into the FHA package.

5.0           References

·       FM Global Data Sheets

·       National Fire Protection Association (NFPA) Codes and Standards, Current Editions

·       International Building Codes

·       DOE STANDARD 1066-2016, Fire Protection

6.0           Revision History

rev

summary

date

0.4

triennial review; added – ‘subcontractor’ to the FPE reference; Note: to section 3.0; removed ‘Provide further evaluation…’ bullet from 4.3.3; updated 5.0; made general edits and format updates

05.19.2022

0.3

periodic review; removed reference to Chapter 6730, Water Quality Management (no longer exists)

06.02.2016

0.2

added equivalencies paragraphs 4.3.1. and 4.3.2; updated links

09.17.2013

0.1

added “Equivalencies and Exemptions” considerations

11.21.2011

0.0

initial document

09.28.2009

 

 

 

 

ISSUING AUTHORITY

AUTHOR

APPROVAL DATE

NEXT REVIEW DATE

rev

 

 

Fire Protection Department

Tim Minga

05.19.2022

05.19.2025

0.4

 

This document is controlled as an online file.  It may be printed but the print copy is not a controlled document. 

It is the user’s responsibility to ensure that the document is the same revision as the current online file.  This copy was printed on 5/19/2022.